Product Features
· Input/output opto-isolation
· Configurable as input or output
· Overvoltage and short-circuit protection functions
· Designed in accordance with IO-Link v1.1 specification, supporting COM3 communication speed
· Supports IO-Link secondary expansion
Product Parameters
type 4 AI,8*M12 8 AI,8*M12
model CM008SEL-4IA CM008SEL-4IV
interface type Extended Connection (IN) M12 A-CODE four-core male connector *1
Extended Connection (OUT) M12 B-CODE five-core female connector *1
Power Connection Powered by the IO Link port at 24 V, 1.6 A
Signal Connection M12 A-CODE five-core female connector *8
Electrical Parameters service voltage DC 24V
Consumption Current ≤50mA
Input Channels Route 4 (X01-X04) Route 8 (X01-X08)
Input Signal Type 0~20mA
input impedence For current input: 250 Ω; for voltage input: 1 MΩ Up to 16 channels, NPN output
resolution ratio 16 bit
change-over time Less than 300 μs
certainty of measurement ±0.3%
Extension Distance You can expand by up to 3 additional Link Bus slaves (up to 1 Link Bus analog/temperature slave), with a total connection length of 60 meters.
IO-Link Parameters interface type CLASS A
edition IO-Link V1.1
transmission speed COM2 (38.4 kbps) or COM3 (230.4 kbps)
Process Data Byte 11 input bytes, 3 output bytes
diagnose Communication Status LED Indication, Communication Message
Power Supply Monitoring Low Voltage Alarm
Short Circuit/Overload Protection LED indicate
environmental resistance levels of protection IP67
ambient temperature Temperatures range from-20°C to +60°C, without freezing.
ambient humidity At 40 to 85% RH, no condensation occurs
antiknock characteristics Acceleration: 500 m/s², applied five times in each direction (X, Y, Z).
vibration resistance 10–55 Hz, composite amplitude 1.5 mm; 2 hours each for the X, Y, and Z axes
Shell Material ABS+PC (polycarbonate)
outline dimension 160mm(H)*60mm(W)*37mm(D)
Product Weight 278g
accessories of a product not have
Product Dimensions
Product Dimensions
Wiring Diagram
Wiring Diagram